This XeteX project showcases the one of seven custom dedicated outdoor air systems for a university.
Unique features include an energy efficient aluminum crossflow flat plate heat exchanger, packaged DX cooling with hot gas reheat, and an indirect gas fired furnace.
Let's take a look at performance and see what's inside.
Model: XHS-30-60-RT-BP-DX-HG-HI-RC-AC
Dimensions: 108”H x 348”L x 110”W
Weight: 16,500 lbs
Supply CFM: 15,000 CFM
Energy Recovery: Aluminum Crossflow Flat Plate Heat Exchanger
Energy Effectiveness: Winter: 59% / Summer: 54%
Heating Types/Heating Capacities:
Indirect Gas Fired Furnace: 475 MBH
Hot Gas Reheat: 317 MBH
Cooling Type: Evaporator (AC)
Cooling Capacity: 64 Tons
A. OA 4” MERV 8 filters on aluminum rack
B. Face and bypass damper
C Aluminum flat plate HX
D. DX coil
E. Blower inlet damper
F. SA premium two fan plenum array
G. Hot gas reheat coil
H. 409 SS indirect fired gas furnace
I. RA 4” MERV 8 filters on aluminum rack
J. Recirc damper
K. Blower inlet damper
L. EA premium two fan plenum array
M. Air-cooled condensing section
N. Compressors