Designed for a hospital, this XeteX custom roof top unit (RTU) is equipped with 150 tons packaged DX air cooled refrigeration for 30k CFM.
This custom RTU features a humidifier manifold, hot gas reheat, indirect gas fired furnace, and high efficiency filters for indoor air quality and year-round climate control.
PERFORMANCE
Model: XAH-30000-RT-RC-DX-HG-HI-HU-FF-AC
Dimensions: 136”H x 573”L x 205”W
Weight: 48,000 lbs
Supply CFM: 30,000 CFM
Heating Types/Capacities:
Hot Gas Reheat: 781 MBH
Humidifier Manifold: 2,279 MBH
Indirect Gas Fired Furnace: 884 MBH
Cooling Type: DX Evaporator Coil
Cooling Capacity: 150 Tons
CONSTRUCTION
- Outdoor unit; manufactured with six-unit sections
- Thermal break construction with 4” double wall casing; injected foam (R-value 28) insulation
- 20ga galvanneal exterior casing with acrylic paint
- 18ga galvanized interior casing
- Welded 8” c-channel structural steel base frame with acrylic paint
- 16ga galvanized floors with 4” injected foam (R-value 28)
- Floors include 2” upturn lip, watertight
- 1/8” aluminum tread plate floor
- 304 SS liner in humidifier and cooling coil sections
FEATURES
- Integral air-cooled section with multiple staged compressors and VFD
- Factory mounted and programmed controls
- Vestibule with 3kw electric heater
- SCCR: 65 kAIC
- Motor removal i-beams in SA/EA fan sections
- SA/EA Piezo flow rings and transducers
- Test ports on each door
COMPONENTS
A. Recirc damper
B. OA 2” MERV 8 filters
C. Evaporator (DX) coil
D. Hot gas reheat coil
E. SA blower inlet damper
F. SA six premium plenum fan array
G. SA motor removable ibeam
H. Heater bypass damper
I. 409 SS indirect fired gas furnace
J. Humidifier manifold
K. SA 12” MERV 15 filters
L. EA blower inlet damper
M. EA four premium plenum fan array
N. EA motor removable ibeam
O. Condensing section
P. Vestibule heater
Q. Split sections
Learn more about XeteX Custom Air Handling Solutions!