This XeteX custom energy recovery ventilator (ERV) delivers 12,500 CFM, 30 tons packaged DX cooling, and up to 70% energy effectiveness for a medical laboratory. It features an epoxy-coated aluminum crossflow plate heat exchanger, modulating face and bypass damper, packaged DX refrigeration, indirect gas-fired furnace, and high efficiency MERV filtration for year-round climate control and indoor air quality. ￼

## Performance

Model: XHS-50-90-RT-BP-DX-HI-FF-AC  
Dimensions: 98”H x 124”W x 278”L  
Weight: 14,500 LBS  
Supply CFM: 12,500 CFM  
Cooling Type: DX Evaporator Coil  
Cooling Capacity: 360 MBH/30 Tons  
Heating Type: Indirect Gas Fired Furnace  
Heating Capacity: 495 MBH   
Energy Recovery: Epoxy-coated Sensible-Only Plate Heat Exchanger  
Energy Effectiveness: 70% Winter / 62% Summer

Construction

- Outdoor unit
- 2” double wall construction with injected foam insulation (R-14) 
    - 20ga galvanneal exterior casing with gray acrylic paint
    - 18ga galvanneal interior casing
- 8” structural steel welded frame and lifting lugs
- Galvanneal floors with 2” injected foam insulation (R-6.9/in)

## Features

- **Epoxy-coated aluminum plate heat exchanger**
- **Packaged DX refrigeration**
- **Factory-mounted Carel DDC programmed unit controls**
- Stainless steel liner in the exhaust tunnel
- PIEZO flow rings
- SA monitor pressure only PIEZO transducer
- Lab exhaust plumes by others

## Components

**A. AC section**  
**B. Epoxy-coated aluminum plate heat exchanger**  
**C. Modulating face & bypass damper**  
**D. SA 4” MERV 13 final filter with galvanized rack**  
**E. OA 2” MERV 8 filters with galvanized rack**  
**F. Air-cooled VFD compressor**  
**G. 409 stainless steel indirect gas-fired furnace**  
**H. SA two premium plenum fan array with PIEZO flow rings**  
**I. Air source DX cooling coil**  
**J. RA 2” MERV 8 filters with stainless steel rack  
**

## Learn more about XeteX custom energy recovery ventilation

<https://xetex.com/hs/cta/wi/redirect?encryptedPayload=AVxigLLGVeJ8Cn3Y3CsTLo5CWOYXHMr%2BlapC9WrW5fUWCkZopNxVAX%2FrDfPNK4yrZkeZtbLiY1HDSiSDmfuTgKLubjfqK%2FpED0NJNZGfX7I6gUa4vAHN2M25VG3%2B0w5jMy7x6w4h6dyjvQnO01ajesePu3jkpezKfKZFFwb7dRvZRnuy2vWm8VeqtwmigOdpPxELIsEFczt2KxyDl0U%3D&webInteractiveContentId=182218501957&portalId=22651078>

[View full post](https://xetex.com/blog/eru-with-packaged-dx-indirect-gas-fired-burner-epoxy-coated-hx)

```json
{
  "@context" : "http://schema.org",
  "@type" : "BlogPosting",
  "author" : {
    "@type" : "Person",
    "name" : "XeteX"
  },
  "dateModified" : "2025-08-01T18:15:16.397Z",
  "datePublished" : "2024-05-08T12:00:16Z",
  "headline" : "Medical Lab Receives an Energy Recovery Ventilator with 30 Tons Cooling",
  "image" : {
    "@type" : "ImageObject",
    "height" : 337,
    "url" : "https://22651078.fs1.hubspotusercontent-na1.net/hubfs/22651078/XeteX%20Blog%20features/XeteX-custom-ERU-with-Packaged-DX-Indirect-Gas-Fired-Burner-and-Coated-HX.jpg",
    "width" : 800
  },
  "mainEntityOfPage" : "https://xetex.com/blog/eru-with-packaged-dx-indirect-gas-fired-burner-epoxy-coated-hx",
  "publisher" : {
    "@type" : "Organization",
    "logo" : {
      "@type" : "ImageObject",
      "height" : 60.0,
      "url" : "https://22651078.fs1.hubspotusercontent-na1.net/hubfs/22651078/XeteX%20logo/XeteX%20with%20tag%20250px.png",
      "width" : 178.57143
    },
    "name" : "XeteX Air Handling Blog"
  }
}
```