This XeteX project features five large outdoor energy recovery units to help tackle this casino’s ventilation challenges.

800x655-13787-Hollywood-Casino-ERU

Casinos face the challenge of introducing large amounts of outside air while ensuring filtered and temperature-controlled environments to provide a welcoming and comfortable environment for patrons.

Conditioning the outside air is the most energy intensive portion of an HVAC system. To help reduce energy consumption, each unit was equipped with an AiRotor 3A energy recovery wheel which offers up to 72% energy recovery effectiveness.

Additionally, the energy wheel was specially coated with an acrylic polymer to reduce exhaust air contaminants from “sticking” to the face of wheel. This will ensure long-lasting wheel performance and continued unit energy savings.

Specifications

  • Model:  AVR-3200-RT-CD-HG-HG-HI-AC
  • Height: 144”
  • Width: 142”
  • Length: 330”
  • Weight: 23,800 lbs
  • Supply CFM: 26,000
  • Return/Exh CFM: 27,000
  • Cool type: DX w/ ACCU
  • Cooling capacity: 90 Tons 2 circuits
  • Heating type: Indirect gas heat
  • Heating capacity: 800 MBH output 10:1 turndown
  • Energy Recovery: 3A Enthalpy Wheel

Unit Highlights

  • Outdoor unit with 18-gauge acrylic painted exterior and 20-gauge galvanized interior
  • 2” Double wall injected foam panels with thermal break construction
  • 4” MERV 8 OA filter and 2” MERV 8 RA filter
  • Two evaporator coils with galvanized casing and SS drain pan
  • Hot gas reheat
  • Dual indirect gas fired heaters (10:1 turndown)
  • 3A AIRotor enthalpy energy recovery wheel
    • Acrylic polymer coating
  • Supply Air—two fan array (direct drive)
  • Exhaust Air—two fan array (direct drive)

Casino-drawings