XeteX Custom RTU with Energy Recovery, Indirect-Fired Heating, and DX Cooling
Designed for a university application, this custom XeteX rooftop unit (RTU) provides...
reliable year-round ventilation, energy recovery, heating, and cooling. The unit features an AHRI-certified desiccant wheel energy recovery system, indirect-fired gas heating, and two-circuit DX cooling for efficient and dependable operation. A thermally broken 3” double-wall casing with injected foam insulation, aluminum interior, wash-down capable floor, and durable exterior finish provide long-lasting protection for outdoor installation. Direct-drive fans with VFD control and flexible airflow connections complete the system for reliable performance.
Let's take a look at performance and see what's inside.
Performance
Model: AVR-1800-RT-BP-RC-DX-HI-AC
Dimensions: 132”H x 444”L x 130”W
Weight: 26,000 lbs
Supply CFM: 23,000 CFM
Heating Types/ Heating Capacities: Indirect Fired
Cooling Type: DX Cooling Coil
Cooling Capacity: 929.5 MBH
Energy Recovery: Enthalpy Wheel
Energy Effectiveness: Winter: 77.7% / Summer: 74.8%
Construction
-
Outdoor unit with thermal break construction
-
3” double-wall construction and injected foam insulation (R-value 6.9/in)
-
18ga painted galvanneal steel exterior with peaked roof; 0.063” aluminum interior casing
-
Welded 8” steel base frame with custom acrylic paint and extended lifting lugs
-
Aluminum drain pan with MPT connection
-
0.063” aluminum treadplate floor with 3” injected foam insulation (R-value 6.9/in)
-
Aluminum thermal break construction doors
Features
-
AHRI-certified 3Å molecular sieve desiccant wheel energy recovery system
-
20:1 modulating indirect-fired 409 stainless steel gas furnace
-
Direct-drive supply and exhaust fans with VFD control
-
R-454B DX cooling with two refrigeration circuits
-
Thermally broken 3” double-wall casing with injected foam insulation
-
0.063” aluminum interior casing
-
Wash-down aluminum floor with drains
-
Peaked roof with durable XeteX Gray exterior finish
-
Outdoor and exhaust air hoods with galvanized bird screens
-
Bottom supply and return duct connections
Components
A. Air Cooled Condensing Section
B. EA 2 fan array
C. SA 2 fan array
D. DX Coil with SS casing
E. Return Air Bypass Damper
F. Backdraft Damper
G. OA 4” MERV 8 Filter with aluminum racking
H. RA 4” MERV 8 Filter with aluminum racking
I. Enthalpy Wheel
J. Built-in Electrical Cabinet
K. Indirect Fired Gas Burner with Controls Vestibule and Exhaust Flues

Learn more about XeteX Custom Air Handling.